东华大学学报(英文版)2001,Vol.18Issue(2):60-67,8.
Numerical Simulation and Experimental Studies of Air Treatment Process with Water Spray of One Row Parallel Flow
Numerical Simulation and Experimental Studies of Air Treatment Process with Water Spray of One Row Parallel Flow
倪波1
作者信息
- 1. College of Environmental Science & Engineering, Dong Hua University, Shanghai, 200051, P.R. China
- 折叠
摘要
Abstract
The main purpose of the present work is to make a further insight into the procedure of heat and mass transfer between water droplets sprayed and air stream in a direct evaporative air cooler used in air-conditioning system in textile mills. The thermodynamic models of the two-phase flow in such a air treatment system have been developed for one row parallel flow spray.The fields of temperature and relative humidity in spraylchamber, as well as the trajectories of sprayed drops have been obtained by calculation. A series of experiment aiming at quantifying the system performance and its influence factors have been conducted. It indicates that the increases of air velocity and water/air ratio while the decrease of nozzle density are favorable. Finally, the comparison between numerical simulation and experimental results have been carried out. Good agreements have been found for outlet air temperaturewhile a maximum error of 10% has been observed for air relative humidity.关键词
heat and mass transfer/air washer/evaporative air cooling/adiabatic humidifyingKey words
heat and mass transfer/air washer/evaporative air cooling/adiabatic humidifying分类
轻工纺织引用本文复制引用
倪波..Numerical Simulation and Experimental Studies of Air Treatment Process with Water Spray of One Row Parallel Flow [J].东华大学学报(英文版),2001,18(2):60-67,8.