东华大学学报(英文版)2007,Vol.24Issue(1):79-84,6.
Selection of Heat Recovery Ventilators in Different Climate Zones of China
Selection of Heat Recovery Ventilators in Different Climate Zones of China
摘要
Abstract
Considering four different climate zones in China, an investigation on the choice of heat recovery ventilator for the buildings with little moisture emissions is carried out. The annual composition of energy consumption of air intake for per unitary air ventilation flow rate is evaluated by employing the testing data of climatic parameters in eight selected cities. The analysis shows that the total heat recovery is suitable in a controlled ventilation system with air humidity controlled during heating period of all the climates. For the building without air humidity controlled in winter, the sensible heat recovery ventilators can be used in severe cold and cold regions, and total heat recovery systems are more suitable for energy saving in hot summer and cold winter and hot summer and warm winter regions.关键词
heat recovery ventilator/sensible heat/latent heat/climate zone/heat recovery effectivenessKey words
heat recovery ventilator/sensible heat/latent heat/climate zone/heat recovery effectiveness分类
建筑与水利引用本文复制引用
ZHONG Ke,ZHAO Jing-de,LIU Jia-ping..Selection of Heat Recovery Ventilators in Different Climate Zones of China[J].东华大学学报(英文版),2007,24(1):79-84,6.基金项目
National Natural Science Foundation of China(Grant No. 50578034 )and Shanghai Educational Development Foundation titled"Shuguang Project"(Grant NO. 03SG30) (Grant No. 50578034 )