Simulation Analysis on the Commutation Failure and Power Recovery Characteristic of an Actual DC Transmission System

洪潮1

作者信息

  • 1. 南方电网科学研究院,广州,510080
  • 折叠

摘要

Abstract

In order to evaluate the security and stability of AC/DC hybrid power systems, it is necessary to explore the interaction between the DC transmission systems and the embedded AC system during commutation failure and DC power recovery.By using a real-time simulaton tool, which can precisely simulate the DC main circuit and its control and protection system, and taking an actual HVDC system in China Southern Power Grid as a test case, this paper evalutes the influence factors on the occurrence of commutation failure of inveter after AC system faults.The results show that the magnitude of three-phase or single-phase voltage drop is the key factor for the occurrence of commutation failure of DC system after three-phase or single-phase to ground faults occur.

关键词

直流输电/换相失败/功率恢复/实时仿真

Key words

DC transmission/ commutation failure/ power recovery/ real-time simulation.