南方电网技术2011,Vol.5Issue(1):1-7,7.
直流输电系统换相失败和功率恢复特性的工程实例仿真分析
Simulation Analysis on the Commutation Failure and Power Recovery Characteristic of an Actual DC Transmission System
摘要
Abstract
In order to evaluate the security and stability of AC/DC hybrid power systems, it is necessary to explore the interaction between the DC transmission systems and the embedded AC system during commutation failure and DC power recovery.By using a real-time simulaton tool, which can precisely simulate the DC main circuit and its control and protection system, and taking an actual HVDC system in China Southern Power Grid as a test case, this paper evalutes the influence factors on the occurrence of commutation failure of inveter after AC system faults.The results show that the magnitude of three-phase or single-phase voltage drop is the key factor for the occurrence of commutation failure of DC system after three-phase or single-phase to ground faults occur.关键词
直流输电/换相失败/功率恢复/实时仿真Key words
DC transmission/ commutation failure/ power recovery/ real-time simulation.分类
信息技术与安全科学引用本文复制引用
洪潮..直流输电系统换相失败和功率恢复特性的工程实例仿真分析[J].南方电网技术,2011,5(1):1-7,7.