| 注册
首页|期刊导航|电力系统保护与控制|云广直流系统交流滤波器保护误动作分析及改进措施

云广直流系统交流滤波器保护误动作分析及改进措施

罗宇航 张振华 张文 郝志杰

电力系统保护与控制2011,Vol.39Issue(3):137-140,4.
电力系统保护与控制2011,Vol.39Issue(3):137-140,4.

云广直流系统交流滤波器保护误动作分析及改进措施

Analysis on mai-operation of AC filter protection and its improvement measure in Yun-Guang HVDC transmission system

罗宇航 1张振华 2张文 1郝志杰1

作者信息

  • 1. 南方电网超高压输电公司广州局,广东,广州,510405
  • 2. 许继日立公司,河南,许昌,461000
  • 折叠

摘要

Abstract

Aiming at the frequent AC filter protection trip in Yun-Guang HVDC transmission system, the root cause of inconsistent protection operation is analyzed according to the hardware configuration of protection device.Based on analyzing the data of transient fault recorder, it is found that there is difference between delay time and protection device operation time in the aspect of delay-setting.Improvement measure on time delay is proposed and simulation experiment and on-spot fault recorder playback experiment are made on RTDS.The simulation results show that the improved protection can avoid the mai-operation caused by impact current effectively.

关键词

电阻基波过流保护/冲击电流/延时补偿/RTDS

Key words

resistor fundamental wave over-current protection/ impact current/ time-delay compensation/ RTDS

分类

信息技术与安全科学

引用本文复制引用

罗宇航,张振华,张文,郝志杰..云广直流系统交流滤波器保护误动作分析及改进措施[J].电力系统保护与控制,2011,39(3):137-140,4.

电力系统保护与控制

OA北大核心CSCDCSTPCD

1674-3415

访问量0
|
下载量0
段落导航相关论文