| 注册
首页|期刊导航|电力系统保护与控制|复杂多机系统次同步振荡的分析与抑制

复杂多机系统次同步振荡的分析与抑制

徐衍会

电力系统保护与控制2011,Vol.39Issue(11):83-89,7.
电力系统保护与控制2011,Vol.39Issue(11):83-89,7.

复杂多机系统次同步振荡的分析与抑制

Analysis and damping of subsynchronous oscillation in complex multi-machine system

徐衍会1

作者信息

  • 1. 新能源电力系统国家重点实验室(华北电力大学)北京,102206
  • 折叠

摘要

Abstract

Subsynchronous oscillation resulting fiom the interaction between complex multi-machine system and HVDC is analyzed and damped. Firstly, the turbine generator units that have SSO problem are screened out using unit interaction factor method. Then,the complex multi-machine system is simplified into single-machine AC-DC hybrid system according to the principle of UIF invariability and the damping characteristic of AC-DC hybrid system is analyzed by complex torque coefficient method. Finally, the HVDC supplemented subsynchronous damping controller designed for single-machine system is used to damp the subsynchronous oscillation of the complex multi-machine system and the simulation results indicate that the SSDC designed in this paper is effective.

关键词

高压直流/次同步振荡/阻尼特性/仿真

Key words

HVDC/ subsynchronous oscillation/ damping characteristic/ simulation

分类

信息技术与安全科学

引用本文复制引用

徐衍会..复杂多机系统次同步振荡的分析与抑制[J].电力系统保护与控制,2011,39(11):83-89,7.

电力系统保护与控制

OA北大核心CSCDCSTPCD

1674-3415

访问量0
|
下载量0
段落导航相关论文