电力系统自动化2011,Vol.35Issue(8):12-15,71,5.
从巴西电网"2·4"大停电事故看继电保护技术应用原则
Analyzing Principle of Protection Through the Blackout in Brazil Power Grid on February 4, 2011
刘宇 1舒治淮 1程逍 1张胜祥1
作者信息
- 1. 国家电力调度通信中心,北京市,100031
- 折叠
摘要
Abstract
On February 4, 2011, a blackout occurred in Northeast of Brazil. The process of blackout is introduced and analyzed. An error of an electronic component in the relay equipment aroused the false action of the breaker failure protection in the substation Luiz Gonzaga and resulted in the blackout finally. With reference to the blackout incident in Brazil, the deficiency of the breaker failure logic adopted in Brazil power grid is analyzed, and the standard breaker failure logic developed by State Grid Corporation of China is also analyzed. The analysis results reveal that the standard logic can avoid the occurring of similar incidents.关键词
巴西电网/大停电/保护装置/安全稳定/开关失灵保护Key words
Brazil power grid/blackout/relay equipment/security and stability/breaker failure protection引用本文复制引用
刘宇,舒治淮,程逍,张胜祥..从巴西电网"2·4"大停电事故看继电保护技术应用原则[J].电力系统自动化,2011,35(8):12-15,71,5.