某风电场风力发电机组振动故障探究
Study on WTG faults caused by turbine vibration
任彦忠 1王川1
作者信息
- 1. 中广核风力发电有限公司,北京,100070
- 折叠
摘要
Abstract
Vibration alarms frequently triggered at the wind speed of 10 to 14 m/s led to the wind turbine generator(WTG)shutdown or a wind farm.After inspection of the WTG, possibility of quality problems was eliminated.To clear the fault,a digital filter was added to the WTG control system to condition the generator speed signal.By feeding the filtered speed signal into the speed control loop,the fault was cleared as expected.Due to the independence of the signalconditioning module,WTG performances were not degraded at all.Field tests indicate that the modified control system can eliminate vibration alarms and improve WTG performances.关键词
风力发电机组/振动/滤波器分类
信息技术与安全科学引用本文复制引用