电力系统及其自动化学报2011,Vol.23Issue(2):81-84,4.
一起电压互感器反充电事件的分析
Analysis of One Potential Transformer Anti-charging Incident
刘剑勇 1胡岸武 2朱志杰2
作者信息
- 1. 华北电力大学电气与电子工程学院,保定,071003
- 2. 江西省电力公司超高压分公司,南昌,330029
- 折叠
摘要
Abstract
PT anti-inverse charge is always happen in power system. The detail process and causes of a 220 kV bus PT anti-inverse charge incident at a 500 kV substation were analyzed in the paper. Then three types switch relays principles were described using circuit figures,and the differences of requirements in the complexity of loop, the reliability of auxiliary contacts and the performance of relay reset coil were compared. Combining their advantages,an single-position self-maintaining switch approach was proposed. Studies indicate that adding an additional small capacity air breaker in the switch circuit is a better way to avoid anti-inverse charge.关键词
母线/电压互感器/继电器/反充电Key words
bus bar/ potential transformer/ relay/ anti-inverse charge分类
信息技术与安全科学引用本文复制引用
刘剑勇,胡岸武,朱志杰..一起电压互感器反充电事件的分析[J].电力系统及其自动化学报,2011,23(2):81-84,4.