高电压技术2011,Vol.37Issue(1):1-7,7.
绝缘子污秽闪络的统计特性及风险评估
Statistical Characteristic and Risk Assessment of Polluted Insulators Flashover
摘要
Abstract
A lot of artificial pollution tests were experimentally investigated in the fog chamber for two kinds of insulators, XP-160 and LD-120 insulators, a large number of test data were obtained, and flashover risk comprehensive assessment based on leakage current amplitude (Im) and flashover voltage (Uf) of polluted insulators was also established. The results show that; probability functions of both amplitude of leakage current (Im) and flashover voltage (Uf) can be described with the normal distribution. Statistical characteristic and pollution flashover risk prediction for transmission line insulators based on leakage current and flashover voltage are given, and flashover probability of polluted insulators of transmission line is calculated.关键词
绝缘子/泄漏电流/闪络概率/统计特性/输电线路/风险评估Key words
insulators/leakage current/flashover probability/statistical properties/transmission line/risk assessment分类
信息技术与安全科学引用本文复制引用
文习山,蓝磊,蒋日坤..绝缘子污秽闪络的统计特性及风险评估[J].高电压技术,2011,37(1):1-7,7.基金项目
重庆大学输配电装备及系统安全与新技术国家重点实验室开放研究基金(2007DA10512709404). (2007DA10512709404)