高电压技术2011,Vol.37Issue(2):497-504,8.
750kV输电线路光纤复合架空地线损耗分析
Analysis on OPGW Grounding Loss on 750 kV AC Transmission Line
摘要
Abstract
On transmission line, OPGW is usually grounded at every tower. With a larger capacity and higher level of load current than 500 kV and lower voltage class transmission line,the 750 kV AC transmission line has a great loop current which will bring about great OPGW grounding losses if it is grounded at every tower. Consequently, the induced voltage and current on the OPGW of 750 kV AC transmission line were simulated and calculated by ATP/EMTP modeling, and three different OPGW grounding modes were comparatively studied. Moreover, the induced voltage and current were on-spot measured. The measurement results are well in agreement with calculation results, and the transposition grounding mode can greatly reduce the grounding loss of OPGW and can be a reference for the design transmission line.关键词
750/kV/OPGW/接地方式/接地损耗/仿真计算/换位接地Key words
750 kV/ OPGW/ grounding mode/ grounding loss/ simulation calculation/ transposition grounding分类
信息技术与安全科学引用本文复制引用
刘凯,吴田,施荣,肖宾,刘庭..750kV输电线路光纤复合架空地线损耗分析[J].高电压技术,2011,37(2):497-504,8.基金项目
国家电网公司科技项目(SGKJJSKF[2008]505). (SGKJJSKF[2008]505)