| 注册
首页|期刊导航|高压电器|An Improved Algorithm of Grounding Grids Corrosion Diagnosis Based on Total Least Square Method

An Improved Algorithm of Grounding Grids Corrosion Diagnosis Based on Total Least Square Method

ZHANG Ying-jiao NIU Tao WANG Sen

高压电器2011,Vol.47Issue(5):22-29,8.
高压电器2011,Vol.47Issue(5):22-29,8.

An Improved Algorithm of Grounding Grids Corrosion Diagnosis Based on Total Least Square Method

An Improved Algorithm of Grounding Grids Corrosion Diagnosis Based on Total Least Square Method

ZHANG Ying-jiao 1NIU Tao 1WANG Sen1

作者信息

  • 折叠

摘要

Abstract

A new model considering corrosion property for grounding grids diagnosis is proposed, which provides reference solutions of ambiguous branches. The constraint total least square method based on singular value decomposition is adopted to improve the effectiveness of grounding grids' diagnosis algorithm. The improvement can weaken the influence of the model's error, which results from the differences between design paper and actual grid. Its influence on touch and step voltages caused by the interior resistance of conductors is taken into account. Simulation results show the validity of this approach.

关键词

corrosion property/ grounding grids/ corrosion diagnosis/ ambiguous/ total least square/touch and step voltages

Key words

corrosion property/ grounding grids/ corrosion diagnosis/ ambiguous/ total least square/touch and step voltages

分类

信息技术与安全科学

引用本文复制引用

ZHANG Ying-jiao,NIU Tao,WANG Sen..An Improved Algorithm of Grounding Grids Corrosion Diagnosis Based on Total Least Square Method[J].高压电器,2011,47(5):22-29,8.

高压电器

OA北大核心CSCDCSTPCD

1001-1609

访问量0
|
下载量0