一起220kV线路高阻接地故障跳闸分析
Analysis of a 220 kV Line Trip Caused by High-resistance Earthing
孙立存 1熊炬 1陈照强 1李新 1李清恩1
作者信息
- 1. 河南省电力公司信阳供电公司,信阳464000
- 折叠
摘要
Abstract
The protective action behaviors of a 220 kV transmission line at both sides are analyzed, on which a trip fault occurred due to high-resistance earthing. This breakdown is an unusual non-typical developing fault in the electrical power system inducing complex protective actions at both sides of the fault. It seems that the protective actions at both sides of the fault were inconsistent and were even misoperation, however, the protective actions are proved correct according to the principles of the WXH-803A and RCS-902BF devices and the further analysis of the oscillograph.关键词
高阻接地/发展性故障/保护动作/录波图/分析Key words
high-resistance earthing/ developing fault/ protection action/ oscillograph/ analysis分类