| 注册
首页|期刊导航|高压电器|干式空心电抗器匝间绝缘检测原理及试验分析

干式空心电抗器匝间绝缘检测原理及试验分析

江少成 马明 戴瑞海 夏晓波 陈荣柱 季凌武 林琳 林坚 陈谢杰 张海龙

高压电器2011,Vol.47Issue(6):67-71,5.
高压电器2011,Vol.47Issue(6):67-71,5.

干式空心电抗器匝间绝缘检测原理及试验分析

Principle and Analysis on Inter-turn Insulation Detection of Dry-type Air-core Reactor

江少成 1马明 1戴瑞海 1夏晓波 1陈荣柱 1季凌武 1林琳 1林坚 1陈谢杰 1张海龙1

作者信息

  • 1. 温州电力局,温州325000
  • 折叠

摘要

Abstract

The electromagnetic parameters of the dry-type air-core reactor are calculated by the finite element method in this paper, which contain serf inductance, mutual inductance, and eddy-current loss. The overall changing patterns of the dry-type air-core reactor's inductance are analyzed under different frequency source with inter-turn insulation defects. An effective method of impulse-voltage test to detect the inter-turn insulation defects within reactor is proposed based on the experimental results. Moreover, the testing method is actually implemented on a set of device to detect the reactor's insulation defects, which is also extensively discussed in the paper. Under conditions of good quality and short-circuit of inter-turn insulation in the reactor, the waveforms of its voltage and current are compared to examine the proposed method. The final result validates the effectiveness of the impulse-voltage test technique.

关键词

干式空心电抗器/匝间绝缘/脉冲电压法/电感/衰减振荡

Key words

dry-type air-core reactor/ inter-turn insulation/ impulse-voltage test methods/ inductance/ attenuation oscillation

分类

信息技术与安全科学

引用本文复制引用

江少成,马明,戴瑞海,夏晓波,陈荣柱,季凌武,林琳,林坚,陈谢杰,张海龙..干式空心电抗器匝间绝缘检测原理及试验分析[J].高压电器,2011,47(6):67-71,5.

高压电器

OA北大核心CSCDCSTPCD

1001-1609

访问量0
|
下载量0
段落导航相关论文