| 注册
首页|期刊导航|高电压技术|1000kV交流紧凑型输电线路潜供电流和恢复电压计算分析

1000kV交流紧凑型输电线路潜供电流和恢复电压计算分析

娄颖 戴敏 何慧雯 李振强

高电压技术2011,Vol.37Issue(8):1882-1887,6.
高电压技术2011,Vol.37Issue(8):1882-1887,6.

1000kV交流紧凑型输电线路潜供电流和恢复电压计算分析

Secondary Arc Current and Recovery Voltage of 1000 kV AC Compact Ti'ansmission Line

娄颖 1戴敏 1何慧雯 1李振强1

作者信息

  • 1. 国网电力科学研究院,武汉430074
  • 折叠

摘要

Abstract

The characteristics of 1000 kV AC compact transmission line are discussed, and the calculating results of secondary arc current and recovery voltage of 1000 kV AC compact transmission line using EMTP under different conditions such as the different length of the transmission line, the compensation factor, transposition, are preSen- ted. Simulation results show that the neutral reactor for HV shunt reactors can effectively limit the second arc cur- rent and recovery voltage, and the principle of selection of neutral reactor must take both insulation level and re- straint of second arc current together with recovery voltage into consideration. It is required that the time of reclos- ing should be 0. 7 s, the length of compact transmission line be 100 km to 500 kin, and the degree of compensation be 95 %, instead of 70 %. However, the influence of transposition, compared with random factors such as environ- ment, or the cost of construction of transposition tower, is negligible. The transposition is not recommended for compact transmission line.

关键词

1000/kV/特高压紧凑型输电线路/潜供电流/恢复电压/线路长度/补偿度/线路换位

Key words

1000 kV/UHV compact transmission line/secondary arc current/recovery voltage/length of the line/compensation/line transposition

分类

信息技术与安全科学

引用本文复制引用

娄颖,戴敏,何慧雯,李振强..1000kV交流紧凑型输电线路潜供电流和恢复电压计算分析[J].高电压技术,2011,37(8):1882-1887,6.

基金项目

国际科技合作项目(2008DFR600lO). ()

高电压技术

OA北大核心CSCDCSTPCD

1003-6520

访问量0
|
下载量0
段落导航相关论文