高电压技术2011,Vol.37Issue(8):2059-2064,6.
绕组布置对变压器式可控电抗器谐波抑制的影响
Influence of Winding Arrangement on Harmonic Suppression for Controllable Reactor of Transformer Type
摘要
Abstract
Two kinds of different arrangements on harmonic-suppressed winding with LC filters are analyzed on the basis of the principle of controllable reactor of transformer type(CRT) with simplex control winding. Harmonic- suppressed winding may be placed between working winding and controlling winding, and the controlling winding may be placed either between working winding and harmonic-suppressed winding. The theoretical analysis of the short circuit reactance of two different arrangements and the harmonic equivalent circuit of three-winding transform- er reveals that the effect of harmonic-suppressed winding is optimum when the harmonic-suppressed winding is placed between working winding and controlling winding. The MATLAB model of CRT with harmonic-suppressed winding is established. It is revealed that the analysis results of winding arrangement are consistent with simulation ones, and the designed CRT has better performance.关键词
变压器式可控电抗器(CRT)/短路电抗/等效电路/绕组布置/谐波抑制/仿真分析Key words
controllable reactor of transformer type(CRT)/short circuit reactance/equivalent ciruit/arrangement ofwinding/harmonic suppression/simulation分类
信息技术与安全科学引用本文复制引用
顾生杰,任恩恩,田铭兴..绕组布置对变压器式可控电抗器谐波抑制的影响[J].高电压技术,2011,37(8):2059-2064,6.基金项目
甘肃省自然科学基金(096RJZA092). ()