| 注册
首页|期刊导航|高压电器|油纸绝缘局部放电超高频检测方法的研究

油纸绝缘局部放电超高频检测方法的研究

李梅

高压电器2011,Vol.47Issue(8):38-42,47,6.
高压电器2011,Vol.47Issue(8):38-42,47,6.

油纸绝缘局部放电超高频检测方法的研究

Ultra-high-frequency Detection Technique for Partial Discharge in Oiled-paper Insulation

李梅1

作者信息

  • 1. 安徽理工大学,淮南232001
  • 折叠

摘要

Abstract

Conventional on-line detection methods of partial discharge are interfered by surroundings, therefore some simulation models of typical partial discharge in transformers are constructed in laboratory, and the models are measured by both UHF narrowband and UHF wideband detection systems. The measurements indicate that for the UHF narrowband detection technique, the central frequency and the bandwidth of the measured signal are adjustable, so optimum central frequency and bandwidth can be selected to avoid interferences; and the UHF wideband detection technique can detect much partial discharge information due to its wider frequency band.

关键词

局部放电/超高频/窄带测量/宽带测量

Key words

partial discharge/ ultra-high-frequency/ narrowband detection/ wideband detection