南方电网技术2011,Vol.5Issue(3):69-72,4.
BP-2B保护装置死区保护的隐患分析及其逻辑优化
The Hidden Failure of BP-2B Numerical Bus-Bar Protection and Its Logic Optimization
黄有立 1崔志文1
作者信息
- 1. 广东电网公司深圳供电局,广东 深圳 518000
- 折叠
摘要
Abstract
It happened in practice that when dead zone failures occurred in certain conditions, the BP-2B protection would make miscarriage of justice so to expand the outage dimension. Aiming at the hidden failure, this paper does analysis and finds out it is due to the logic of bus connection pre-closed, putting forward an improvement scheme for the logic so to avoid the maloperation of non failure bus and to limit the outage dimension, and thus to have certain engineering value.关键词
微机母线保护/母联断路器预投/母联死区保护/充电保护Key words
microcomputer-based bus protection/ bus connection pre-closed/ bus-bar dead zone protection/ charge protection分类
信息技术与安全科学引用本文复制引用
黄有立,崔志文..BP-2B保护装置死区保护的隐患分析及其逻辑优化[J].南方电网技术,2011,5(3):69-72,4.