摘要
Abstract
A method of precaution control based on optimal dispatch of generation is proposed. Firstly, all potential faults of the net are scanned and then the no-harmful faults are excluded. Ranked by the product of EEAC stability margin and fault probability, the critical cluster group of potentially harmful fault can be identified. Secondly, the limit of power adjustment, △pmin and △pmax, can be determined with EEAC sensitivity analysis method. Thirdly, the ratios of active power adjustment of the generators are determined according to the number of critical generators and the sensitivity of the stability margin to generator output. Finally, the optimization of precaution control can be transformed into the optimal output dispatch of generators which are chosen in last step. Simulation results in New England 10-generator 39-bus system show the feasibility and correctness of this method.关键词
发电量最优分配/扩展等面积准则/灵敏度分析/暂态稳定/预防控制Key words
optimal generation dispatch/ EEAC/ sensitivity analysis/ transient stability/ preventive control分类
信息技术与安全科学引用本文复制引用