陈渝士 1陶亦寿1

作者信息

  • 1. 长江科学院武汉长江仪器自动化研究所,武汉430010
  • 折叠

摘要

Abstract

The excessive fault current induced by stator single-phase earth fault and big ground capacitance of stator winding of large generator can be restricted by neutral grounding through distribution transformer. This paper introduces a configuration method of generator neutral grounding device with high impedance distribution transformer. The fault capacitive current is partly compensated by the inductive current generated from the internal reactance of the transformer, and the ground-fault current is limited within an allowable range while the fault transient overvolt-age is restrained.

关键词

发电机中性点/接地装置/高阻抗变压器/配置方法

Key words

generator neutral/ grounding device/ high impedance transformer/ configuration method