| 注册
首页|期刊导航|高压电器|一起110kV避雷线发热问题的分析和处理

一起110kV避雷线发热问题的分析和处理

许飞 韦巍 李恒灿 农宇

高压电器2011,Vol.47Issue(9):113-116,120,5.
高压电器2011,Vol.47Issue(9):113-116,120,5.

一起110kV避雷线发热问题的分析和处理

Analysis and Treatment of a Heating Fault of 110 kV Lightning Wire

许飞 1韦巍 1李恒灿 1农宇2

作者信息

  • 1. 广西电网公司电力科学研究院,南宁530023
  • 2. 广西电网公司百色供电局,百色533000
  • 折叠

摘要

Abstract

Field survey and analysis were performed about a lightning wire heating fault of 110 kV Maping traction line into Pingguo traction substation. It was found that the heating was generated by exceeding ground reflux current due to the missing of a length of reflux line. Simulation of the traction substation by the software CDEGS shows that greater traction current appears in lightning wire when traction load is larger. A test in the traction substation verifies the correctness of the analysis. In addition, some suggestions are offered to ensure safe operation of the traction substation.

关键词

牵引站/避雷线/发热/CDEGS

Key words

traction substation/ shielding wire/ heating/ CDEGS

分类

信息技术与安全科学

引用本文复制引用

许飞,韦巍,李恒灿,农宇..一起110kV避雷线发热问题的分析和处理[J].高压电器,2011,47(9):113-116,120,5.

高压电器

OA北大核心CSCDCSTPCD

1001-1609

访问量0
|
下载量0
段落导航相关论文