流体机械2011,Vol.39Issue(7):1-5,5.DOI:10.3969/j.issn.1005-0329.2011.07.001
改变叶轮与蜗壳相对安装位置对双吸多翼风机性能影响的试验研究
Experimental Study on the Effect of Relative Impeller-to-volute Position on the Performance of Multi-blade Centrifugal Fan
摘要
Abstract
An experimental structure which can adjust the installation positions of the impeller and the volute was devised to investigate the effect of relative impeller-to-volute position on the performance of a multi-blade centrifugal fan which is widely used in the terminal unites of central air conditioning. The results show that the coincident position between the impeller center and the volute geometric center was not conducive to the performance of this test fan. An optimum relative impeller-to-volute position can enhance the volume flow rate and the total efficiency of the fan by 6.08% and 2.4% each, while the sound pressure level was decreased by 0.8dB(A).关键词
多翼离心风机/叶轮与蜗壳相对安装位置/试验研究Key words
multi-blade centrifugal fan/relative impeller-to-volute position/experiment study分类
机械制造引用本文复制引用
杨昕,陈望明,袁民建,温选锋,何明杰..改变叶轮与蜗壳相对安装位置对双吸多翼风机性能影响的试验研究[J].流体机械,2011,39(7):1-5,5.基金项目
省部产学研结合项目:盘管风机设计方法及节能降噪研究(2009B90300031) (2009B90300031)