| 注册
首页|期刊导航|电测与仪表|配电混合线路双端行波测距方法的研究

配电混合线路双端行波测距方法的研究

李配配 范炜龙 黄家栋

电测与仪表Issue(12):48-52,5.
电测与仪表Issue(12):48-52,5.

配电混合线路双端行波测距方法的研究

The Study on the Fault Location Based on Double Ended Traveling Wave Method in Hybrid Lines in Distribution Network

李配配 1范炜龙 2黄家栋1

作者信息

  • 1. 华北电力大学电力系统保护与动态安全监控教育部重点实验室,河北保定071003
  • 2. 河北省送变电公司,石家庄050051
  • 折叠

摘要

Abstract

The propagation of the fault wave is very complex in hybrid lines in distribution network. It is difficult to identify the wave which reflected back from the point of failure by single terminal location method without external signal source so the method is not applicable in this condition. Double ended fault location method only needs to detect the exact time when the initial wave barrier first arrive to the both end of the line and don' t have to consider the refraction and reflection wave. So the results obtained from this method are reliable. But the velocity of wave varied widely in overhead lines and cable lines and this lead to the failure of the traditional double-ended fault location method. For this problem the paper proposed a fault search algorithm based on the variable of time and according to the algorithm we put forward a fault location solution for hybrid lines with branch. At last the effectiveness of the method is proved by ATP simulation.

关键词

配电网/混合线路/双端测距/行波

Key words

network distribution, hybrid lines, double ended fault location method, traveling wave