| 注册
首页|期刊导航|电气技术|特高压输电线路的工频过电压研究

特高压输电线路的工频过电压研究

田书 郭芃君 梁京

电气技术Issue(9):18-21,4.
电气技术Issue(9):18-21,4.

特高压输电线路的工频过电压研究

Research on Power Frequency Over-voltage in UHV Transmission Line

田书 1郭芃君 1梁京1

作者信息

  • 1. 河南理工大学电气工程与自动化学院,河南焦作454003
  • 折叠

摘要

Abstract

The level of over-voltage has an effect on the equipment security in UHV transmission line, based on UHV transmission line project, in this paper applies the domestic and foreign research in UHV power frequency over-voltage. The capacity effect of unloaded line and single-phase grounding fault was investigated, the methods, which influence the over-voltage were simulated and compared by ATP-EMTP. The effect of power frequency over-voltage is analyzed when high voltage parallel reactor is installed different spot and base on installed the high voltage parallel reactor, the effect of single-phase grounding fault over-voltage when the line both side with MOA. Simulation results show that the power frequency over-voltage can be suppressed to 1.135p.u. when properly installing the high voltage parallel reactor on the line; single-phase grounding fault is 1.317p.u. respectively. When MOA are applied the line, the over-voltage can be suppressed to 1.045p.u..

关键词

特高压/工频过电压/高压并联电抗器/金属氧化物避雷器

Key words

UHV: power frequency over-voltage: high voltage parallel reactor: MOA

分类

信息技术与安全科学

引用本文复制引用

田书,郭芃君,梁京..特高压输电线路的工频过电压研究[J].电气技术,2011,(9):18-21,4.

基金项目

河南理工大学实验室开放基金项目(SKJAl0082)河南理工大学研究生学位论6文创新堆金项目. ()