| 注册
首页|期刊导航|电力系统自动化|基于粗糙集的三调谐直流滤波器失谐故障元件检测方法

基于粗糙集的三调谐直流滤波器失谐故障元件检测方法

王钢 罗慧卉 黄敏 李海锋

电力系统自动化2011,Vol.35Issue(20):81-87,7.
电力系统自动化2011,Vol.35Issue(20):81-87,7.

基于粗糙集的三调谐直流滤波器失谐故障元件检测方法

A Rough-set Based Detection Method for Detuning Components in a Triple-tuned DC Filter

王钢 1罗慧卉 1黄敏 1李海锋1

作者信息

  • 1. 华南理工大学电力学院,广东省广州市510640
  • 折叠

摘要

Abstract

The sensitivity analysis reveals the influence of triple-tuned DC filter component parameters on its resonant frequency.Based on that finding,a detuning detection method for triple-tuned DC filter is proposed according to the rough-set theory.In this method,a decision-making table is established,the relative change of harmonic current flowing through DC filter caused by various parameters is condition attribute,and the component type is decision attribute.Detection rules of fault component from the established decision-making table are derived.Finally,the rules of evaluation on the fault location,like the certainty factor,coverage and confidence are discussed.A large number of simulation on the actual DC system shows that the fault locating method is simple and effective.

关键词

三调谐直流滤波器/灵敏度分析/粗糙集/故障元件检测

Key words

triple-tuned DC filter/sensitivity analysis/rough set/detection of fault component

分类

信息技术与安全科学

引用本文复制引用

王钢,罗慧卉,黄敏,李海锋..基于粗糙集的三调谐直流滤波器失谐故障元件检测方法[J].电力系统自动化,2011,35(20):81-87,7.

基金项目

国家科技支撑计划重大项目 ()

粤港关键领域重点突破项目(2009A091300011)~~ ()

电力系统自动化

OA北大核心CSCDCSTPCD

1000-1026

访问量0
|
下载量0
段落导航相关论文