Abstract
The sensitivity analysis reveals the influence of triple-tuned DC filter component parameters on its resonant frequency.Based on that finding,a detuning detection method for triple-tuned DC filter is proposed according to the rough-set theory.In this method,a decision-making table is established,the relative change of harmonic current flowing through DC filter caused by various parameters is condition attribute,and the component type is decision attribute.Detection rules of fault component from the established decision-making table are derived.Finally,the rules of evaluation on the fault location,like the certainty factor,coverage and confidence are discussed.A large number of simulation on the actual DC system shows that the fault locating method is simple and effective.关键词
三调谐直流滤波器/灵敏度分析/粗糙集/故障元件检测Key words
triple-tuned DC filter/sensitivity analysis/rough set/detection of fault component分类
信息技术与安全科学引用本文复制引用
王钢,罗慧卉,黄敏,李海锋..基于粗糙集的三调谐直流滤波器失谐故障元件检测方法[J].电力系统自动化,2011,35(20):81-87,7.基金项目
国家科技支撑计划重大项目 ()