During the test and operation of Suidong converter station in Yunnan-Guangdong DC transmission project, the fault tripping of resistance fundamental over-current protection is analyzed which resulted to the bipole block of UHVDC project. The reason of this accident is given according to the transient fault records (TFR) of protection equipment and the oscilloscope. The different results are acquired in the same algorithm with different TFR. Two methods are given to solve this problem and proved by RTDS test. When these methods are utilized in future China UHVDC control and protection system, the UHVDC can operate better.

关键词

交流滤波器/电阻基波过流保护/误动作/采样率

Key words

AC filter/ resistance fundamental over-current protection/ fault trip/ sample rate

分类

信息技术与安全科学

引用本文复制引用

田庆..云广特高压直流输电工程穗东站交流滤波器电阻基波过流保护误动作分析[J].高压电器,2012,48(2):7-11,5.

基金项目

感谢南网科研院郭琦、贾旭东、黄立滨在 RTDS试验验证上的大量工作. ()