Analysis of a Burned-out Failure of Transformer Bushing

王伟 1韩金华 1郭运明 2赵磊 1王震宇1

作者信息

  • 1. 河南电力试验研究院,郑州450052
  • 2. 安阳供电公司,安阳455000
  • 折叠

摘要

Abstract

In this paper, according to the test phenomenon and field inspection, a typical burned-out failure of 550 kV transformer bushing in Henan Power Grid is introduced. The cause of the burned-out failure of the transformer bushing is found out to be insufficient pull of the draw rod through the disassembled inspection and structure analysis of the failed bushing. Relevant preventive measures such as testing pull force of draw rod and strengthening the technical exchange between manufacturers and users are provided.