河南理工大学学报:自然科学版2011,Vol.30Issue(6):709-713,5.
商场中庭机械排烟数值模拟研究
Numerical research on smoke exhaust in one shopping mall with atrium
摘要
Abstract
At present,the method of the quantity of smoke exhaust calculated by code for fire protection design of tall buildings has some problems.Combining with Jin-Ying atrium in a shopping mall,makes design of smoke exhaust in atrium using fire performance-based design method,and makes simulation of smoke control effect using FDS(Fire Dynamics Simulator).The results indicate that the quantity of smoke exhaust 443 520 m3/h calculated by the fire performance-based design method can make staff safety evacuation.关键词
商场中庭/机械排烟/性能化设计/FDSKey words
atrium/shopping mall/mechanical smoke exhaust/performance-based design/FDS分类
建筑与水利引用本文复制引用
裴蓓,牛国庆,刘华..商场中庭机械排烟数值模拟研究[J].河南理工大学学报:自然科学版,2011,30(6):709-713,5.基金项目
长江学者和创新团队发展计划项目 ()
河南省科技计划项目 ()
河南省教育厅自然科学研究计划项目 ()