南方电网技术2011,Vol.5Issue(4):78-80,3.
一起高压输电线路直流融冰感应过电压分析
Case Analysis of Inductive Over-Voltage Occurred on an HV Transmission Line During DC De-Icing
曾华荣 1张迅 1吕黔苏 1傅闯2
作者信息
- 1. 贵州电力试验研究院,贵阳550002
- 2. 南方电网科学研究院,广州510080
- 折叠
摘要
Abstract
Aiming at the problem of inductive over-voltage occurred on 500 kV Yaxi-Fuquan Transmission Line Ⅱ during DC de-icing,this paper does theoretical calculation and actual tests,resulting in a conclusion that this inductive over-voltage is caused by the disruptive discharge of the over-voltage protection gap on the DC de-icing line due to the inductive voltage perturbation of parallel-operating transmission lines,and it can be overcome in a way to change the de-icing method,or to adjust the gap distance settings of the rectifier device.关键词
直流融冰/感应过电压/并行输电线路/融冰方式/保护间隙Key words
DC de-ice/inductive voltage/across parallel transmission lines/ice melting method/protection gap分类
信息技术与安全科学引用本文复制引用
曾华荣,张迅,吕黔苏,傅闯..一起高压输电线路直流融冰感应过电压分析[J].南方电网技术,2011,5(4):78-80,3.