南方电网技术2011,Vol.5Issue(5):81-85,5.
配电网混合线路单相弧光接地故障检测新方法
A New Detection Approach for Single-Phase Arc Grounding Fault of Distribution Mixed Feeders
摘要
Abstract
The transient quanlity is the most significant features when a fault occurs.But its short duration makes it difficult to de-tect the fault.Because of the transient zero sequence current contains a large number of high harmonic,which up to a cycle dura-tion,the paper presents a novel algorithm for single phase arc grounding fault location of distribution network.The Habedank arc modle is built.According to analyse the spectral characteristics of the transient zero-sequence current,the feature band is found.The amplitude and direction of transient zero-sequence current within the feature band is filtrated to detect the arc grounding fault.Simulation results demonstrate that the proposed algorithm is fast and accurate anti-jamming of the good characteristic.关键词
配电网/故障检测/Habedank电弧模型/特征频带Key words
distribution network/fault detection/habedank arc-model/feature band分类
信息技术与安全科学引用本文复制引用
张宗包,袁荣湘,倪林..配电网混合线路单相弧光接地故障检测新方法[J].南方电网技术,2011,5(5):81-85,5.基金项目