天广工程直流线路突变量保护误动作分析

田庆

高压电器2012,Vol.48Issue(4):33-38,6.
高压电器2012,Vol.48Issue(4):33-38,6.

天广工程直流线路突变量保护误动作分析

Analysis on the Fault Trip of Bipole DC Line Protection in Tianguang HVDC

田庆1

作者信息

  • 1. 南方电网超高压输电公司检修试验中心,广州510663
  • 折叠

摘要

Abstract

This paper analyses three bipole line protection accidents after the completion of the Tianguang HVDC control and protection regenerated system. The reason of DC line dU/dt protection fault trip is given according to the transient fault record in Tianshenqiao converter station and Guangzhou converter station. The set value of dU/ dt protection and the setting process are studied in order to understand the fault trip. Two corresponding methods, lowing the under voltage protection value and increasing the dU/dt protection value, are put forward which are proved by the field effect. When these methods are utilized in future China home-produced HVDC control and protection system, the HVDC can operate better.

关键词

天广直流/突变量保护/双极线路保护动作

Key words

Tianguang HVDC/ dU/dt protection/ bipole DC line protection trip