高压电器2012,Vol.48Issue(4):106-110,5.
一例500kV断路器重合闸不成功情况分析
Accident Analysis for a Unsuccessful 500 kV Circuit Breaker Reclosing
摘要
Abstract
By analyzed the case of unsuccessful reclosing situation of a 500 kV circuit breaker, the reasons of the fault was due to the improper value of the circuit breaker's low pressure interlocking settings.When the temperature of external environment sudden droped, low pressure interlocking relay action, leading to the unsuccessful reclosing of the circuit breaker. The paper developed a corresponding coping strategies according to the reason, that was adjusting the value of low pressure interlocking settings to the appropriate ones, ensure that the circuit breaker could operate normally and action correctly to adapt to different operating conditions. And protect the operation of the equipment and grid safely and stablly.The strategies achieved good results, for preventing and dealing with similar fault it was of a certain significance.关键词
断路器/跳闸/重合闸/液压机构/压力闭锁Key words
circuit breaker/ tripping/ reclosing/ hydraulic mechanism/ low pressure interlocking分类
信息技术与安全科学引用本文复制引用
樊越甫,刘国辉,王军峰,钟代宁..一例500kV断路器重合闸不成功情况分析[J].高压电器,2012,48(4):106-110,5.