| 注册
首页|期刊导航|流体机械|部分负荷率对热泵系统能耗的影响分析

部分负荷率对热泵系统能耗的影响分析

于齐东

流体机械2012,Vol.40Issue(1):76-80,5.
流体机械2012,Vol.40Issue(1):76-80,5.DOI:10.3969/j.issn.1005-0329.2012.01.018

部分负荷率对热泵系统能耗的影响分析

Part Load Ratio on the Impact of Energy Consumption of Heat Pump System

于齐东1

作者信息

  • 1. 天津城市建设学院,天津300384
  • 折叠

摘要

Abstract

In cold areas part - load ratio of single building energy consumption were studied problem, select the air - cooled heat pump water loop heat pump with two air - conditioning system for the study. In the energy consumption of the two heat pump system based on the theory of comparative analysis, with 100% , 80% , 60% , 40% , 20% part load ratio five - speed power engineering test run throughout the year, and based on the use of part of the test results Dimensionless rate of energy consumption of the load analysis of the test data are analyzed. The results from the testing and analysis show that: part - load impact rate on the water loop heat pump is greater than air - cooled heat pump, especially in the winter; air - cooled heat pump and part - load ratio has a linear relationship, the water loop heat pump and some non - linear loading rate relations, water loop heat pump operating point aberration in 80% and 100% load segment range.

关键词

水环热泵/风冷热泵/部分负荷率/无因次曲线

Key words

heat pump/air-cooled heat pump/part of the loading rate/non-dimensional curve

分类

化学化工

引用本文复制引用

于齐东..部分负荷率对热泵系统能耗的影响分析[J].流体机械,2012,40(1):76-80,5.

流体机械

OA北大核心CSCDCSTPCD

1005-0329

访问量0
|
下载量0
段落导航相关论文