| 注册
首页|期刊导航|南方电网技术|220kV分级绝缘变压器中性点保护配置探讨

220kV分级绝缘变压器中性点保护配置探讨

张霖 杨超

南方电网技术2011,Vol.5Issue(z1):75-78,4.
南方电网技术2011,Vol.5Issue(z1):75-78,4.

220kV分级绝缘变压器中性点保护配置探讨

On the Neutral Point Protection Configuration of 220 kV Graded Insulation Transformers

张霖 1杨超1

作者信息

  • 1. 贵阳供电局,贵阳550001
  • 折叠

摘要

Abstract

To choose a proper neutral point protection for 220 kV graded insulated transformer, the paper analyzes the protection configuration of arrester and discharge gap for the neutral point of 220 kV graded insulated transformer. According to the situation of Guizhou Power Grid, in which its 220 kV un-earthed transformer of neutral point grounding system adoptes coordinated protection by metal oxide arrester (MOA) and protective gap, the paper calculates the protection gap of the transformer's neutral point, takes weather factor into consideration, and concludes that a maximum protection gap should be selected to prevent frequent operation, and meets the over-voltage protection requirements.

关键词

分级绝缘变压器/中性点/避雷器/保护间隙

Key words

graded insulated transformer/ neutral point/ surge arrester/ protective gap

分类

信息技术与安全科学

引用本文复制引用

张霖,杨超..220kV分级绝缘变压器中性点保护配置探讨[J].南方电网技术,2011,5(z1):75-78,4.

南方电网技术

OACSTPCD

1674-0629

访问量0
|
下载量0
段落导航相关论文