测试方法对MOA避雷器泄漏电流特性的影响

王颂 叶建铸 左干清 刘红太

南方电网技术2011,Vol.5Issue(z2):22-26,5.
南方电网技术2011,Vol.5Issue(z2):22-26,5.

测试方法对MOA避雷器泄漏电流特性的影响

The Influence of Test Method on the Characteristics of MOA's Leakage Current

王颂 1叶建铸 1左干清 1刘红太1

作者信息

  • 1. 中国南方电网超高压输电公司广州局,广州510405
  • 折叠

摘要

Abstract

There are two off-line test methods for the leakage current of MOAs in HVDC systems, namely the demolition connection method and the non-demolition connection method. The former has an advantage to detect accurately the MOA's reference voltages of U1mA and 75%U1mA while the latter can do the detection very fast and directly. But there is a question, "if the results of the two methods are equivalent", that facing operation departments and testers. With the two methods this paper does a field test on the lightning arrester of convertor in Guizhou-Guangdong +500 kV HVDC transmission system, and analyzes the leak current characteristics of the arrester in various situations, founding that the results with these methods are basically in agreement, and then discusses the feasibility and diversity of the two methods.

关键词

高压直流输电/避雷器/泄漏电流/拆连接线法/不拆连接线法

Key words

HVDC transmission/lightning arrester/leakage current/demolition connection method/non-demolition connection method