高海拔500kV交流滤波断路器外绝缘特性

吕刚 陆岩 田应富

南方电网技术2011,Vol.5Issue(z2):37-40,4.
南方电网技术2011,Vol.5Issue(z2):37-40,4.

高海拔500kV交流滤波断路器外绝缘特性

The Outer Insulation Characteristics of ac 500 kV Filter Circuit Breaker at High Altitude

吕刚 1陆岩 1田应富1

作者信息

  • 1. 中国南方电网超高压输电公司贵阳局,贵阳550003
  • 折叠

摘要

Abstract

Flash faults of ac filters at Gaopo substation of Guizhou-Guangdong 500 kV HVDC transmission system have heppened many times. The mechanism of the flash is analyzed in this paper, and through artificial contamination tests for displaying the voltage change of flash the cause of these flash faults is discovered as follows: The outer insulation of filthy circuit breaker's arc-chute lowered by the inclement weather condition in the high altitude area. Furthermore, countermeasures against the flash of filthy circuit breaker are proposed based on the experimental results.

关键词

闪络/污秽/交流滤波器/断路器

Key words

flash/filthy/ac filters/circuit breaker

分类

信息技术与安全科学