中国电机工程学报2011,Vol.31Issue(z1):217-221,5.
1036MW机组汽动引风机控制策略优化及其深度节能研究
Research on Optimizing the Control Strategy and Deepening the Energy Conservation of Steam-driven Draft Fans in 1 036 MW Unit
孙叶柱 1孙伟鹏 2江永2
作者信息
- 1. 华能国际电力股份有限公司,北京市西城区100031
- 2. 华能海门电厂,广东省汕头市515132
- 折叠
摘要
Abstract
Configuration of steam-driven draft fan system was introduced, the adjusting functions and the energy-saving performance of the stream driven draft fans as well as the problems encountered in its actual operation were analyzed, eventually, some relevant solutions were proposed. Due to the impact of external load, the million-kilowatt unit designed in accordance with its base-load by Huaneng Haimen Power Plant frequently varies between 400 MW and 1036 MW in a day. It is necessary to optimize the opening of stator blades in steam-driven draft fans and the coordination of rotational speeds among small stream turbines in the whole unit. Through practice, the whole control strategy of steam-driven draft fans of 1036 MW unit in Huaneng Haimen Power Plant was optimized. Not only the security of instant run bank for failures the steam-driven draft fans but also the instant reaction ability to the furnace negative pressure was enhanced and improved. Meanwhile, the logically modified stator blades of steam-driven draft fans runs basically within the maximum efficiency area of draft fans. Thus, the aim of deepening the energy conservation of stream-driven draft fans was achieved. It is of great referential value for the design and logical optimization of steam-driven fan system.关键词
1036MW机组/汽动引风机/控制策略/逻辑优化/节能Key words
1036 MW units/ steam-driven draft fans/control strategy/ operation optimization/ energy conservation分类
信息技术与安全科学引用本文复制引用
孙叶柱,孙伟鹏,江永..1036MW机组汽动引风机控制策略优化及其深度节能研究[J].中国电机工程学报,2011,31(z1):217-221,5.