一起变压器低压侧故障跳开中压侧母联断路器原因的分析

冯毅 王少杰 田文平 王亚杰

电力系统自动化2012,Vol.36Issue(9):113-115,3.
电力系统自动化2012,Vol.36Issue(9):113-115,3.

一起变压器低压侧故障跳开中压侧母联断路器原因的分析

Analysis of Bus Tie Circuit Breaker Tripping in Medium Voltage Side Caused by Transformer Fault in Low Voltage Side

冯毅 1王少杰 1田文平 1王亚杰2

作者信息

  • 1. 宁夏电力公司吴忠供电局,宁夏回族自治区吴忠市751100
  • 2. 西安交通大学电气工程学院,陕西省西安市710049
  • 折叠

摘要

Abstract

The impact on operation of backup protection in medium voltage side caused by phase to phase short circuit fault in low voltage 10 kV bus side of 110 kV transformer is analyzed.Then,corresponding solutions such as fitting backup protection time,changing operation mode of system,etc,are proposed for reducing influence of low voltage side phase to phase fault on backup protection in medium voltage side.Through failure model simulation and theoretical calculation,the feasibility of previous solutions is verified,which may offer a reference for the setting calculation of power system.

关键词

变压器/后备保护/母联断路器/分列运行/整定计算

Key words

transformer/backup protection/bus tie circuit breaker/parallel operation/setting calculation