| 注册
首页|期刊导航|电子器件|基于Hyperlynx的变电站状态监测无线节点信号完整性仿真分析

基于Hyperlynx的变电站状态监测无线节点信号完整性仿真分析

吴超 吴明赞 李竹

电子器件2012,Vol.35Issue(2):173-176,4.
电子器件2012,Vol.35Issue(2):173-176,4.DOI:10.3969/j.issn.1005-9490.2012.02.013

基于Hyperlynx的变电站状态监测无线节点信号完整性仿真分析

Signal Integrity Simulation Analysis of Substation Condition Monitoring Wireless Node Based on Hyperlynx

吴超 1吴明赞 1李竹1

作者信息

  • 1. 南京理工大学自动化学院,南京210094
  • 折叠

摘要

Abstract

Because of the high-speed circuit existed in the design of vrtreless node PCB of the substation condition monitoring system,signal integrity problems is inevitable. The reflection and crosstalk of key signals in wireless node is simulated with HyperLynx and IBIS model. Without any suppression measures, reflections and crosstalk has a great impact on signals. The overshoot and undershoot amplitude is mucn larger than 200 mV and maximun crosstalk amplitude is 370 mV. By series termination and increase in the transmission line spacing,decrease in the coupling length,the impact of reflection and crosstalk on signal can be significantly reduced. So it meets the signal integrity requirements.

关键词

信号完整性/反射/串扰/HyperLynx/无线节点

Key words

signal integrity reflection/ crosstalk/ HyperLynx/ wireless node

分类

信息技术与安全科学

引用本文复制引用

吴超,吴明赞,李竹..基于Hyperlynx的变电站状态监测无线节点信号完整性仿真分析[J].电子器件,2012,35(2):173-176,4.

电子器件

OA北大核心CSTPCD

1005-9490

访问量0
|
下载量0
段落导航相关论文