高电压技术2012,Vol.38Issue(3):762-768,7.
用于60Hz电力系统的高压直流换流阀运行试验等效方法
Equivalent Method of Operational Test for HVDC Thyristor Valve Used in 60 Hz Electric Power Systems
许钒 1周会高 1张长春 1胡治龙 1刘朴 1黄熹东1
作者信息
摘要
Abstract
To ensure reliable operation of the high voltage direct current(HVDC) projects,operational tests of thyristor valves must be carried out.As the operating frequency is subject to the power system frequency,how to test products at different frequency is a serious problem.Adopting the Xi'an High Voltage Apparatus Research Institute(XIHARI) 50 Hz operational test circuit as a basis for meeting the requirements of operational test for valves in 60 Hz system,we studied and compared the current,voltage,other electrical parameters and the loss characteristics of the valves,and proposed an equivalent method and the equivalent parameters of operational test for valves in 60 Hz system by a 50 Hz test circuit.The results show that it is feasible to test a converter valve in different frequency synthetic operational test circuits,but appropriate equivalent is needed for different test items.The equivalent method provides a reference for research and test of the HVDC systems in different frequencies.关键词
60Hz电力系统/高压直流(HVDC)/换流阀/运行试验/等效方法/折算系数Key words
60 Hz electric power systems/high voltage direct current(HVDC)/thyristor/operational test/equivalent method/equivalent parameter分类
信息技术与安全科学引用本文复制引用
许钒,周会高,张长春,胡治龙,刘朴,黄熹东..用于60Hz电力系统的高压直流换流阀运行试验等效方法[J].高电压技术,2012,38(3):762-768,7.