高压电器2012,Vol.48Issue(3):117-122,6.
500kV变压器瓦斯保护误动分析及整改
Malfunction Analysis of a 500 kV Transformer Gas Relay with Countermeasure
摘要
Abstract
For a malfunction of heavy gas protection of a 500 kV transformer, the structure and working principle of the gas relay are described. Investigation and calculation indicate that this malfunction of the gas relay is due to blockage of the dehydrating breather, negative pressure in the oil tank, and improper structure of the gas collection box. Corresponding emergency measure is put forward, and modification of the gas box is suggested.关键词
瓦斯继电器/误动/低油面保护/集气盒/呼吸器Key words
gas relay/ malfunction/ low oil level protection/ gas box/ dehydrating breather分类
信息技术与安全科学引用本文复制引用