蒲石河抽水蓄能电站发变组继电保护的设计及特点

杨光华 栾德艳 常颖 彭倞

水力发电2012,Vol.38Issue(5):75-77,3.
水力发电2012,Vol.38Issue(5):75-77,3.

蒲石河抽水蓄能电站发变组继电保护的设计及特点

Design of Generator-tranformer Unit Relay Protection and Its Characteristics in Pushihe Pump-storage Power Station

杨光华 1栾德艳 2常颖 1彭倞1

作者信息

  • 1. 中水东北勘测设计研究有限责任公司,吉林 长春130021
  • 2. 辽宁蒲石河抽水蓄能有限公司,辽宁 丹东118216
  • 折叠

摘要

Abstract

The configuration and design of generator-transformer unit relay protection in Pushihe Pump-storage Power Station is introduced herein. The relay protection has characteristics of two sets of protection system stand-by to each other, more reliable software switching, and independent operation without relying on monitoring system. For solving the problems discovered in the commissioning tests, the breaker tripping scheme during back-to-back starting process is optimized, the rotor one-point grounding protection equipment is re-selected, the right operation of stator grounding protection is analysed, and the copper grounding to unit control and protection board is also added. Hie experiences of commissioning tests can be as references to other pumped-storage power stations.

关键词

发变组/继电保护/设计/接地保护/蒲石河抽水蓄能电站

Key words

generator-transformer unit/ relay protection/ design/ grounding protection/ Pusfaihe Pumped-storage Power Station