配线接地雷电感应过电压特征分析

陈绍东 黄智慧 张义军 王建国 李斌 曾昌军 陈杏容

中国电力2012,Vol.45Issue(5):43-47,5.
中国电力2012,Vol.45Issue(5):43-47,5.

配线接地雷电感应过电压特征分析

Characteristics analysis on the lightning induced over voltage and its attenuation factors through metal pipe buried with overhead distribution lines

陈绍东 1黄智慧 1张义军 2王建国 3李斌 1曾昌军 1陈杏容1

作者信息

  • 1. 广东省防雷中心,广东广州510080
  • 2. 中国气象科学研究院,北京100081
  • 3. 武汉大学高电压与绝缘技术研究所,湖北武汉430072
  • 折叠

摘要

Abstract

In order to understand the lightning induced voltage characteristics and actual attenuation effect of buried metal pipe on the possible over-voltage, the waveforms of over voltage before and after buried metal pipe when lighting happens are observed and analyzed. The analysis shows that the shape of over voltage waveform is basically unchanged around SO m after buried metal pipe. However, the magnitude is attenuated. The attenuation factor is mainly related to the distance of lightning. When lighting happens 1 000 m away from the observation place, the attenuation ratio is about 20%. The attenuation ratio is decreased when the distance increases. The average of the attenuation ratio is about 6% when the lightning happens within 3-7 km. Moreover, the attenuation ratio is also related to the direction of lightning.

关键词

架空配电线路/雷电/感应过电压/穿金属管埋地/衰减/回击

Key words

overhead distribution lines/lightning/induced voltage/through pipe buried/attenuation/stroke