摘要
Abstract
In order to verify the safety of switching of gas insulated switchgear (GIS) disconnectors energized in ultra high voltage(UHV) AC Pilot Demonstration Project, we experimentally investigated switching of all GIS disconnectors energized in Changzhi, Nanyang, and Jingmen substations, and monitored very fast transient overvoltage (VFTO) and transient enclosure voltage (TEV) generated . The tests results show that switching of UHV GIS disconnectors energized is safe, the effect of TEV on secondary equipment should be paid attention to, and damping resistor in disconnector can mitigate VFTO and TEV significantly, The tests provide technical support for the future switching of GIS disconnector energized in UHV substations.关键词
特高压(UHV)/气体绝缘金属封闭开关设备(GIS)/复合型气体绝缘金属封闭开关设备(HGIS)/隔离开关/带电操作/特快速暂态过电压(VFTO)/暂态壳体电位(TEV)Key words
ultra high voltage (UHV)/gas insulated switchgear (GIS)/hypid gas insulated switchgear (HGIS)/disconnector/hot-line work/very fast transient overvoltage (VFTO)/transient enclosure voltage (TEV)分类
信息技术与安全科学引用本文复制引用
李志兵,陈维江,王浩,孙岗,张翠霞,刘洪涛,马国明,岳功昌,胡榕,时卫东,孙泽来,张建功..特高压交流试验示范工程GIS隔离开关带电操作试验[J].高电压技术,2012,38(6):1436-1444,9.基金项目
国家重点基础研究发展计划(973计划) ()
国家电网公司科技项目 ()
国家电网公司科技项目(2011)~~ ()