化工进展2012,Vol.31Issue(6):1200-1205,6.
平板式环路热管性能的实验
Experimental investigation on the performance of loop heat pipe with flat evaporator
张先锋1
作者信息
- 1. 中国电子科技集团第三十八研究所,安徽合肥230088
- 折叠
摘要
Abstract
To investigate the effect of condenser location and gravity on operating performance,a miniature loop heat pipe with series flat evaporator were tested.The results show that the loop heat pipe can start up successfully at various positions under a low heat load(20 W) and have good operating performance with Qmax=130 W and R=0.21 /W.At horizontal ℃ al position,the loop heat pipe with shorter vapor line has better start-up performance and higher Qmax.Under a higher heat load,the effect of condenser location on operating performance becomes more noticeable.It is found that a loop heat pipe with series flat evaporator has good anti-gravity capability and can operate with all elevations and tilts.When the loop heat pipe is at vertical position with compensation chamber above the evaporator,its operating performance is the best under the gravity field.关键词
环路热管/平板式蒸发器/冷凝器/反重力性能/运行特性Key words
loop heat pipe/flat evaporator/condenser/anti-gravity capability/operating performance分类
能源科技引用本文复制引用
张先锋..平板式环路热管性能的实验[J].化工进展,2012,31(6):1200-1205,6.