The FBG Temperature Measurement System for XLPE Cable Connector Based on Etalon

刘安文 1王伟2

作者信息

  • 1. 绍兴电力局,浙江绍兴312000
  • 2. 华北电力大学新能源电力系统国家重点实验室,北京102206
  • 折叠

摘要

Abstract

At present, using FBG to measure the temperature of cable is becoming an important means of on-line monitoring and evaluating the insulation of XLPE cable. In this paper, the principle of demodulating measurement results of FBG by F-P filter is introduced, and the inherent defects of this method is pointed out by experiment. To overcome this defect and to improve the measurement accuracy, an F-P etalon is used to detect the drift of wavelength. The F-P etalon can completely avoid the impact of the nonlinear relationship between filtered wavelength and tuning voltage, which improves the accuracy of the fiber Bragg grating. A system with three-phase 110kV XLPE cable connector is measured in laboratory, and the measurement error can be controlled within ± 0. 4 ℃, which shows that the system has good engineering practicability.

关键词

XLPE/标准具/温度/光纤光栅/F-P滤波器

Key words

XLPE/ etalon/ temperature/ fiber Bragg grating (FBG)/ F-P filter