A Low Voltage Ride-through Control Strategy for Direct-driven Permanent Magnet Wind Power Generation System with Flywheel Energy Storage Unit
摘要
Abstract
The operational behavior of the direct-driven permanent magnet synchronous generator (PMSG) wind turbine with flywheel energy storage unit under grid symmetrical fault conditions is analyzed. Based on that, a coordinated control strategy for the generator-side converter, grid-side converter and flywheel motor-side converter is proposed to enhance the low voltage ride-through (LVRT) performance of the whole system. The proposed control strategy can not only keep the DC-link voltage stable, but also deliver proper reactive power from the system to the grid during the network fault, effectively enhancing the LVRT performance. The proposed control strategy is verified by the simulation results. Furthermore, the key factors that influence the LVRT capability are analyzed, and the LVRT ability of the system is assessed.关键词
风力发电/飞轮储能单元/电网对称故障/永磁同步发电机/低电压穿越Key words
wind power generation/flywheel energy storage unit/grid symmetrical fault/permanent magnet synchronous generator (PMSG)/low voltage ride-through (LVRT)分类
信息技术与安全科学引用本文复制引用
姚骏,陈西寅,夏先锋,廖勇,黄嵩..含飞轮储能单元的永磁直驱风电系统低电压穿越控制策略[J].电力系统自动化,2012,36(13):38-44,7.基金项目
国家自然科学基金资助项目 ()
中央高校基本科研业务费专项资金资助项目 ()
输配电装备及系统安全与新技术国家重点实验室自主研究项目 ()