| 注册
首页|期刊导航|电力系统自动化|接地极开路保护的改进

接地极开路保护的改进

徐斌 张颖 赵森林 叶雷

电力系统自动化2012,Vol.36Issue(15):120-123,4.
电力系统自动化2012,Vol.36Issue(15):120-123,4.

接地极开路保护的改进

Improvement of Electrode Line Open Circuit Protection

徐斌 1张颖 2赵森林 1叶雷3

作者信息

  • 1. 南京南瑞继保电气有限公司,江苏省南京市211102
  • 2. 上海交通大学电子信息与电气工程学院,上海市200240
  • 3. 郑州供电公司,河南省郑州市450006
  • 折叠

摘要

Abstract

Electrode line open circuit protection for blocked pole will mal-operate due to the induced voltage caused by the healthy pole line after single pole fault, and then block the healthy pole. To avoid thus situation, an improvement scheme is proposed from both control and protection aspects. In the control aspect, a new pole isolation method is adopted, the line switch is switched off as soon as possible to avoid induced voltage. In the protection aspect, a current criterion is added and consequences of protection operation is also suggested. The feasibility and effectiveness of the scheme is verified by real-time digital simulator (RTDS) based simulation tests.

关键词

高压直流/极隔离/接地极开路保护

Key words

high voltage direct current (HVDC)/pole isolation/electrode line open circuit protection

分类

信息技术与安全科学

引用本文复制引用

徐斌,张颖,赵森林,叶雷..接地极开路保护的改进[J].电力系统自动化,2012,36(15):120-123,4.

电力系统自动化

OA北大核心CSCDCSTPCD

1000-1026

访问量0
|
下载量0
段落导航相关论文