何胜红 1苏杏志 1陈志平 1许澜1

作者信息

  • 1. 广东电网公司佛山供电局试验研究所,佛山528000
  • 折叠

摘要

Abstract

The partial discharge (PD) detection was performed to a 220 kV GIS by the UHF sensing method and the ultrasonic sensing method. A partial discharge was found and located in the arrester chamber. Based on the analysis of the PD signal pattern, a PD of floating part was determined. The detection and diagnosis results were confirmed by the afterward maintance, which provided a valuable sample for the GIS PD on-line detection.

关键词

局部放电/在线检测/GIS/避雷器

Key words

partial discharge/on-line detection/GIS/MOA