抑制电弧炉闪变的STATCOM直接电压控制研究
Research on Direct Voltage Control of STATCOM for Mitigating Electric Arc Furnaces Flicker
刘华东 1张定华 1唐建宇 1邱岳烽1
作者信息
- 1. 南车株洲电力机车研究所有限公司,株洲412001
- 折叠
摘要
Abstract
Aimed at the insufficient capacity of mitigating electric arc furnaces(EAF) flicker problems for the traditional double-closed-loop control mode of static synchronous compensator (STATCOM), this paper calculates the compensation current command which achieves the minimum voltage fluctuation by analyzing the various EAF distribution network voltage and current phasor, and directly calculates the control voltage command according to the principle of the network instantaneous power equal to the STATCOM instantaneous power. So the STATCOM controller is less three PI regulators than the traditional dual-loop control mode, and the response time from the original 20ms is reduced to 10ms, so it improves the ability of voltage flicker suppression. Simulation and actual operatin~ results verify that the orot)osed control strate~v in this naner is effective and correet.关键词
STATCOM/电弧炉/闪变/双闭环控制/直接电压控制Key words
STATCOM/electric arc furnace/flicker/double double-closed-loop control/directvoltage control分类