高电压技术2012,Vol.38Issue(9):2150-2156,7.
特高压交流输电线路潜供电弧的抑制措施
Secondary Arc Extinction Methods for UHVAC Transmission Lines
摘要
Abstract
In order to ensure the successful reclosure of single-phase automatic reclosure on ultra-high voltage transmission lines,the value of the secondary arc current and the recovery voltage must be limited.We analyzed and described two popular secondary extinction methods,namely,one by using high speed grounding switch(HSGS) and another by using the neutral reactor compensation.Taking Zhebei-Shanghai UHVAC double circuit transmission lines on the same tower as an example,we presented the computation of secondary arc current and recovery voltage by ATP/EMTP,and compared the results.The results show that both methods can restrain the value of secondary arc current and recovery voltage.The high speed grounding switch can only be applied to imcomplete transposition and the short transmission lines.The neutral reactor compensation can only be applied to the whole transmission lines.The optimal size of the neutral reactors of shunt reactor is 500 mH.关键词
特高压交流(UHVAC)/快速接地开关(HSGS)/中性点小电抗/潜供电流/恢复电压/单相重合闸Key words
ultra-high voltage alternative current (UHVAC)/high speed grounding switch(HSGS)/neutral reactor/arccurrent/recovery voltage/single-phase reclose分类
信息技术与安全科学引用本文复制引用
林莘,谢寅志,徐建源..特高压交流输电线路潜供电弧的抑制措施[J].高电压技术,2012,38(9):2150-2156,7.基金项目
高等学校博士学科点专项科研基金 ()
教育部高等学校科技创新工程重大项目培育资金项目 ()
辽宁省教育厅项目(2006R40 ()
2008T134) ()